Troubleshooting
SiBE041025
52
Service Diagnosis
4. Troubleshooting
4.1
Error Codes and Description
★
: Displayed only when system-down occurs.
Error Codes
Description
Reference
Page
System
00
Normal
—
U0
★
Refrigerant shortage
U2
Low-voltage detection or over-voltage detection
U4
Signal transmission error (between indoor and outdoor unit)
UA
Unspecified voltage (between indoor and outdoor unit)
Indoor
Unit
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control or heating peak-cut control
A6
Fan motor (DC motor) or related abnormality
C4
Indoor heat exchanger thermistor or related abnormality
C9
Room temperature thermistor or related abnormality
Outdoor
Unit
E1
Outdoor unit PCB abnormality
E5
★
OL activation (compressor overload)
E6
★
Compressor lock
E8
Input overcurrent detection
EA
Four way valve abnormality
F3
Discharge pipe temperature control
F6
High pressure control in cooling
H0
Compressor system sensor abnormality
H6
Position sensor abnormality
H8
DC voltage / current sensor abnormality
H9
Outdoor temperature thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Outdoor heat exchanger thermistor or related abnormality
L3
Electrical box temperature rise
L4
Radiation fin temperature rise
L5
Output overcurrent detection
P4
Radiation fin thermistor or related abnormality