SiBE041025
Troubleshooting
Service Diagnosis
83
Troubleshooting
Check No.06
Refer to P.86
(R11991)
Caution
YES
NG
NO
NO
YES
YES
YES
YES
NO
OK
YES
NO
NO
NO
NO
YES
∗
Discharge pipe thermistor
∗
Indoor or outdoor heat exchanger thermistor
∗
Room temperature thermistor
∗
Outdoor temperature thermistor
Check for refrigerant leakage.
Replace the outdoor unit PCB.
NO
YES
Replace the capillary tube.
Change for a specified amount of
fresh refrigerant.
Replace them
in position.
Open the stop valve.
Repair the pipe flare or
replace the union.
Check the power transistor
harness for looseness.
Correct it as required. Also
replace cracked pipe.
Check the pipes for
improper contact. Correct
them as required. Also
replace cracked pipe.
Replace the defective
one(s).
Completed.
Replace the compressor.
Completed.
Error again?
Oil oozing at internal
piping?
Stop valve closed?
Compressor vibrating
too much?
Oil oozing at relay
pipe connections?
Any thermistor
disconnected?
Check No. 06
Check the thermistors.
Completed.
Error again?
Error again?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.