Main Functions
SiBE041025
20
Function and Control
1.9
Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail
When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Ex.) : POWERFUL operation in cooling mode.
Operation mode
Fan speed
Target temperature
COOL
H tap + 80 rpm
18°C
DRY
DRY rotating speed + 80 rpm
Lowered by 2.5°C
HEAT
H tap + 80 rpm
31°C
FAN
H tap + 80 rpm
—
AUTO
Same as cooling / heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R11981)
Target temp.
Fan
80 rpm
18˚C
POWERFUL ON
POWERFUL OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
20 minutes
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.