Control Specification
SiBE041025
30
Function and Control
2.9
Outdoor Fan Control
1. Fan OFF delay when stopped
The outdoor fan is turned OFF 70 seconds after the compressor stops.
2. Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the compressor
is OFF.
3. Fan OFF control while defrosting
The outdoor fan is turned OFF while defrosting.
4. Fan ON/OFF control when operation starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
5. Fan control while forced operation
The outdoor fan is controlled as well as normal operation while the forced operation.
6. Fan ON/OFF control for pressure difference upkeep
The outdoor fan is controlled for keeping the pressure difference while cooling with low outdoor
temperature.
♦
When the pressure difference is small, the outdoor fan stops.
♦
When the pressure difference is large, the outdoor fan rotates.
2.10 Liquid Compression Protection Function
Outline
In order to obtain the dependability of the compressor, the compressor is stopped according to
the outdoor temperature and temperature of the outdoor heat exchanger.
Detail
Operation stops depending on the outdoor temperature
Compressor turns off under the conditions that the system is in cooling operation and outdoor
temperature is below 0°C.