SiBE061121
Forced Cooling Operation
Trial Operation and Field Settings
131
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit (25/35 class)
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
The forced cooling operation starts when any of the following conditions is
fulfilled.
1) Press the forced cooling operation ON/OFF button (S1W) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor
unit.
Command
frequency
25/35 class: 58 Hz
50 class: 66 Hz
End
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (S1W) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor
unit.
Others
The protection functions are prior to all others in the forced cooling operation.
ON/OFF button (S1W)
(R14649)
1
2
3
Push here
Screwdriver
(R13824)
SiBE061121.book Page 131 Friday, April 22, 2011 4:12 PM