Electrical installation
Installer and user reference guide
104
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
16.1.3 About electrical compliance
This equipment (LREN* and LRNUN5A7Y1) complies with:
▪
EN/IEC 61000‑3‑11
provided that the system impedance Z
sys
is less than or equal
to Z
max
at the interface point between the user's supply and the public system.
-
EN/IEC 61000‑3‑11 = European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a system impedance Z
sys
less
than or equal to Z
max
.
▪
EN/IEC 61000‑3‑12
provided that the short-circuit power S
sc
is greater than or
equal to the minimum S
sc
value at the interface point between the user's supply
and the public system.
-
EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a short-circuit power S
sc
greater
than or equal to the minimum S
sc
value.
Model
Z
max
Minimum S
sc
value
LREN8A7Y1B
–
5477
LREN10A7Y1B
–
5819
LREN12A7Y1B
–
6161
LRNUN5A7Y1
–
2294