16
|
Electrical installation
Installer and user reference guide
108
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
Remote switches
See details in:
▪
"16.5.1 Low voltage wiring – Outdoor unit"
▪
"16.6.1 Low voltage wiring – Capacity up unit"
Output signals
See details in:
▪
"16.5.2 High voltage wiring – Outdoor unit"
▪
"16.6.2 High voltage wiring – Capacity up unit"
16.5 Connections to the outdoor unit
NOTICE
▪
Be sure to keep the power line and transmission line apart from each other
(≥50 mm). Transmission wiring and power supply wiring may cross, but may not
run parallel.
▪
Transmission wiring and power supply wiring may NOT touch internal piping in
order to avoid wire damage due to high temperature piping.
▪
Firmly close the lid and arrange the electrical wires so as to prevent the lid or
other parts from coming loose.
Low voltage wiring
▪
DIII transmission wiring
▪
Remote switches (operation, low noise)
High voltage wiring
▪
Output signals (caution, warning, run,
operation)
▪
Power supply (including earth)
16.5.1 Low voltage wiring – Outdoor unit
Connections/routing/fixing
a
F2
F1
F1
X1M (A1P)
b
F2 Q1 Q2
TO
MULTI UNIT
TO
OUT/D UNIT
TO
IN/D UNIT
c d
2
1
3
X5M
a/b
c/d
X1M (A1P)
X5M
1
2
X1M (A1P)
DIII transmission wiring:
a: To capacity up unit
b: To communication box
X5M
Remote switches:
c: Remote operation switch
d: Remote low noise switch