23
|
Troubleshooting
Installer and user reference guide
141
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
Main code
LREN*
LRNUN5*
Cause
Solution
O
O
Malfunction of discharge/
compressor body temperature
sensor
For LREN*:
▪
(R31T) - A1P (X19A)
▪
(R32T) - A1P (X33A)
▪
(R33T) - A2P (X19A)
▪
(R91T) - A1P (X19A)
▪
(R92T) - A1P (X33A)
▪
(R93T) - A2P (X19A)
For LRNUN5*:
▪
(R3T) - A1P (X19A)
▪
(R9T) - A1P (X19A)
Check connection on PCB or
actuator.
O
O
Malfunction of suction temperature
sensor
For LREN*:
▪
(R21T) - A1P (X29A)
▪
(R22T) - A1P (X23A)
▪
(R23T) - A2P (X29A)
For LRNUN5*:
▪
(R2T) - A1P (X29A)
Check connection on PCB or
actuator.
O
O
Malfunction of the gas cooler outlet
temperature thermistor
For LREN* and LRNUN5*:
▪
(R4T) – A1P (X35A)
Check connection on PCB or
actuator.
O
O
Malfunction of the economizer
outlet temperature thermistor
For LREN*:
▪
(R8T) – A1P (X30A)
For LRNUN5*:
▪
(R6T) – A1P (X35A)
Check connection on PCB or actuator
O
O
Malfunction of the liquid (after sub-
cool) temperature thermistor
For LREN*:
▪
(R7T) – A1P (X30A)
For LRNUN5*:
▪
(R7T) – A1P (X35A)
▪
(R5T) – A1P (X35A)
Check connection on PCB or
actuator.