3
|
Specific installer safety instructions
Installer and user reference guide
18
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from:
▪
101].
▪
The wiring diagram of the outdoor unit, which is delivered with the unit, located
on the inside of the top plate. For a translation of its legend, see
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
WARNING
▪
If the power supply has a missing or wrong N-phase, equipment might break
down.
▪
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪
Install the required fuses or circuit breakers.
▪
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪
Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
▪
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable national wiring regulation.
▪
Make electrical connections to the fixed wiring.
▪
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
category III condition, MUST be installed in the fixed wiring.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3 mm between the contact
point gaps that provides full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.