Installation manual

5

20B7Y1R

Air cooled refrigeration condensing unit

4P360438-1B – 2014.01

1.

An inverter condensing unit may cause electronic noise generated 
from AM broadcasting. Examine where to install the main 
condensing unit and electric wires, keeping proper distances away 
from stereo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is a 
distance of at least 3 meters for indoor remote controllers, place 
power wiring and transmission wiring in conduits, and ground the 
conduits.

2.

When installing in a locations where there is heavy snowfall, 
implement the following snow measures.

• Ensure the base is high enough that intakes are not clogged by 

snow.

• Mount a snowbreak hood (optional accessory)
• Remove the rear intake grille to prevent snow from 

accumulating on the fins.

3.

If condensate may drip on downstairs (or walkway) depending on 
the floor condition, take a measure such as the installation of 
central drain pan kit (sold separately).

4.

The refrigerant R410A itself is nontoxic, nonflammable and is safe. 
If the refrigerant should leak however, its concentration may 
exceed the allowable limit depending on room size. Due to this it 
could be necessary to take measures against leakage. 
See “Engineering Data” for details.

5.

If the outdoor units are installed in areas with heavy snowfall, the 
installation of a snowbreak hood is required. This is available as an 
optional accessory. If the units are installed in a location where the 
ambient temperature can drop below –10°C, install a windbreak 
board or a snowbreak hood.

1.

Snowbreak hood installation

Required parts:

2.

Windbreak board installation

In case no suction-side board is required:

a

Master unit

b

Slave unit

c

Master unit 1

d

Slave unit 1

e

Master unit 2

f

Slave unit 2

g

Wall height unrestricted

In case a suction-side board is required:

a

Master unit

b

Slave unit

c

Wall height unrestricted

Notes:

*1 

Board and wall height: 1300 mm or more.

*2

 If the outdoor units are installed in rows, install side boards on both 

sides of the installation.

a

Master unit 1

b

Slave unit 1

c

Master unit 2

d

Slave unit 2

*3

 If there is no wall opposite the suction side of each outdoor unit, 

install a suction-side board covering all outdoor units.

a

Master unit 1

b

Slave unit 1

c

Wall height unrestricted

*4

 For the installation space around the outdoor units, see 

"3. SELECTION OF LOCATION" on page 3

.

Snowbreak hood

Option names

Required amount

1

Right side air inlet

KPS26C504R

1

2

Left side air inlet

KPS26C504L

1

3

Back side air inlet

KPS26C504B

2

1240

560

200

1680

1290

765

1240

560

560

1290

3

3

2

1

”

”

”

”

”

”

”

a

c

d

e

f

b

*1

g

*1

*2

*1

A

B

C

•

7000

”

3000

”

1500

”

1500

a

b

*1

*1

*3

c

•

1300

•

1300

”

”

”

a

b

c

d

b

a

b

a

c

c

Summary of Contents for LREQ15B7Y1R

Page 1: ...INSTALLATION MANUAL LREQ15B7Y1R LREQ20B7Y1R Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that t...

Page 5: ...containing less than 95 kg refrigerant charge CAUTION This unit is already filled with a certain amount of R410A Never open liquid and gas shutoff valve until the step specified in 9 CHECKS AFTER WOR...

Page 6: ...ber of indoor units be sure to install them at the same level Use either off cycle defrosting or electric heater defrosting as the defrosting type Hot gas defrosting models cannot be used Make sure th...

Page 7: ...for front side no higher than 1500 mm Wall height on the suction side no higher than 500 mm Wall height for sides no limit Make sure each unit is installed level Install the slave unit adjacent to the...

Page 8: ...See Engineering Data for details 5 If the outdoor units are installed in areas with heavy snowfall the installation of a snowbreak hood is required This is available as an optional accessory If the un...

Page 9: ...hen installing on a roof make sure the roof floor is strong enough and be sure to water proof all work Make sure the area around the machine drains properly by setting up drainage grooves around the f...

Page 10: ...used is clean and free of contaminants such as sulphur oxide dust chips oil and fat and water It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m Use the following type of re...

Page 11: ...f indoor units connected downstream Total capacity of indoor units after branching Liquid pipe size less than 4 0 kW 6 4 x 0 8 O type 4 0 kW over and less than 14 0 kW 9 5 x 0 8 O type 14 0 kW over an...

Page 12: ...plete Wait until all oil is dripped out 7 Cut the pinched piping off with a pipe cutter just above the brazing point or just above the marking in case there is no brazing point 8 Wait until all oil is...

Page 13: ...t to the valve cover mount and the screw thread of the service port Otherwise dew condensation water will intrude inside and freeze Therefore refrigerant gas leakage or a compressor malfunction may re...

Page 14: ...nnected at the lateral side bottom CAUTION Only use the dedictated outdoor unit multi connection piping kit EKHRQZM When brazing make sure there are no flammable materials around 1 Connect gas side ac...

Page 15: ...oisture Follow instructions in the dryer instruction manual concerning dryer brazing Repair any burning of dryer paint that occurs during dryer brazing Contact the manufacturer for more information ab...

Page 16: ...to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the...

Page 17: ...field supply 7 3 Procedure for power supply wiring Procedure for Power Supply Wiring 1 Power supply 3 phase 50 Hz 380 415 2 Overcurrent circuit breaker earth leakage circuit breaker all pole disconne...

Page 18: ...stem on page 13 by all means when connecting the operation output wiring A compressor failure may result if the operating output wiring is not connected Remote switch wiring connections When installin...

Page 19: ...ut operation output wiring from the front 10 When routing remote operating switch wiring from the front 11 Remote switch terminal block X3M 12 When routing remote switch wiring through a wiring openin...

Page 20: ...e the outdoor unit for one hour and then check that the reading on the vacuum gauge is not rising If the reading on the vacuum gauge is rising water may be remaining in the system or leakage may be oc...

Page 21: ...page 19 see the illustrations below Use the piping outlet for jobs required during the steps of 10 REFRIGERANT REPLENISHMENT on page 19 e g a job of taking in the charge hose Note After knocking out t...

Page 22: ...n operation d Turn off the operation switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the g...

Page 23: ...in ballpoint or another non conducting object Close the inspection door after the work is finished A Inspection hole upper left B Inspection hole upper right 1 Inspection door left 2 Lift to open 3 Op...

Page 24: ...malfunction code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts b...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P360438 1B 2014 01 Copyright 2013 Daikin 4P360438 1 B 0000000_...

Reviews: