SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
99
6.6.8 “
F3
” Abnormal Discharge Pipe Temperature
Remote
Controller
Display
F3
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level.
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty discharge pipe temperature thermistor
Faulty outdoor unit PCB
Insufficient injection at intermediate heat exchanger outlet caused by flash gas due to gas
leakage or insufficient volume of refrigerant.
Clogging of electronic expansion valve for injection
Failure to open the maintenance valve
Insufficient insulation of onsite suction pipe
or
Discharge pipe temp. >120°C continuously for 70 sec. or more
Discharge pipe temp. >125°C continuously for 30 sec. or more
Discharge pipe temp. >130°C
&
Discharge pipe temp. >110°C
EV2 · pls
≥
450 pls
EV3 · pls
≥
450 pls
continuously for 60 sec.