Troubleshooting
SiENBE28-901
116
Air Cooled Refrigeration Condensing Unit
6.6.19 “
L5
” INV Compressor Instantaneous Overcurrent
Remote
Controller
Display
L5
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Malfunction is detected from the currents flowing in the power transistor.
Malfunction
Decision
Conditions
An overcurrent (59.1A) flows even instantaneously.
Supposed
Causes
Faulty compressor coil (e.g. broken wire or insulation failure)
Compressor startup failure (mechanical lock)
Faulty inverter PCB
Slugging of refrigerant
Abrasion of sliding parts caused by wet operation due to faulty secondary equipment
expansion valve
Failure of oil return due to faulty on site piping work
Liquid return caused by operation signal connection failure