Troubleshooting
SiENBE28-901
118
Air Cooled Refrigeration Condensing Unit
6.6.20 “
L8
” INV Compressor Overload
Remote
Controller
Display
L8
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Malfunction is detected from the currents flowing in the power transistor.
Malfunction
Decision
Conditions
Currents on the secondary side of the inverter come to the following values.
(1) Not less than 19A for a period of consecutive 5 seconds
(2) Not less than 16.1A for a period of consecutive 260 seconds
Supposed
Causes
Compressor overload
Broken wire in compressor coil
Disconnection of compressor wiring
Faulty inverter PCB
Slugging of refrigerant
Abrasion of sliding parts caused by wet operation due to faulty secondary equipment
expansion valve
Failure of oil return due to faulty on site piping work
Liquid return caused by operation signal connection failure