SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
119
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Power OFF
Is the stop
valve open?
Is the
compressor lead
wire normal?
YES
NO
YES
NO
Are wirings and wire
connections to the
compressor
normal?
YES
NO
The insulation
resistance of the
compressor is
not more than
100k
Ω
NO
YES
There is a
broken wire in
the compressor
coil.
NO
YES
Check4
(P.133)
Is the power
transistor
normal?
YES
NO
Open the stop valve.
Replace the compressor lead wire.
Correct the wirings and wire
connections.
Replace the INV compressor.
Replace the INV compressor.
Replace the inverter PCB (A3P).
Connect the compressor
lead wire, and then restart
operation.
The malfunction
"
L8
" recurs.
YES
NO
Is a difference between
high pressure and low
pressure prior to
restarting not more
than 0.2MPa?
YES
NO
Continue the operation.
Faulty pressure equalization in the
refrigerant circuit
Check for compressor