SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
121
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check4
(P.133)
Is the power
transistor
normal?
Is the first time for the
compressor to start after
installation?
YES
NO
Is a proper amount
of refrigerant
charged?
NO
YES
Is the stop
valve open?
NO
YES
Refrigerant is
slugging. (No power
is applied for a period
of not less than 6
hours.)
YES
NO
Is the insulation
resistance of compressor
maintained at not less
than 100k
Ω
?
NO
YES
Is the compressor
lead wire
disconnected?
YES
NO
Refrigerant is
slugging. (No power
is applied for a period
of not less than 6
hours.)
NO
YES
Is the insulation
resistance of compressor
maintained at not less
than 100k
Ω
?
NO
YES
There is a
broken wire in
the compressor.
YES
NO
Charge a proper amount of
refrigerant.
Open the stop valve.
Eliminate the slugging of
refrigerant.
Eliminate the slugging of
refrigerant.
Connect the compressor lead wire.
Rectify, apply power, and then
restart operation.
Recheck for the compressor and
the refrigerant circuit.
Eliminate the slugging of
refrigerant.
Replace the INV compressor.
Replace the INV compressor.
Replace the compressor INV PCB
(A3P).
Recheck the compressor and
refrigerant system.
NO
YES