SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
147
No continuous operations allowed
1. Turn off the operation switch for the outdoor unit. After the outdoor unit has stopped, turn off
the power supply for the outdoor unit.
2. Remove the control box.
3. Close the stop valves in the order: C and D.
4. Recover the refrigerant in the compressor through service ports c, b. (
shaped region.)
∗
After replacing parts, check whether the dryer is WET or DRY using the moisture indicator.
If it is WET, replace the dryer.
5. Conduct air tight checks.
6. Conduct vacuuming through the service port c and b.
(Then charge the refrigerant according to the quantity as that recovered. And then continue
vacuuming.)
7. Turn on the power supply for the outdoor unit. Then turn on the operation switch for the
outdoor unit.
(If a remote controller switch is used, enable the remote setting.)
8. Charge the refrigerant by the same quantity as that recovered.
Applicable parts
• Main electronic expansion valve
• Injection electronic expansion valve
3 compressors
HPSL
HPS1
D
a
C
B
A
b
HP
Td1
INV
EV2
TL
c
EV1
Tg
LP
Tce
HPS3
Td2
EV3
SV2
Ta
HPS2
SV3
Td3
STD1
STD2
Tg
A: Discharge line maintenance valve B: Injection line maintenance valve C: Liquid stop valve
D: Gas stop valve a, b, c: Service ports
Repair or replace the applicable parts.