Appendix (Supplementary Information)
SiENBE28-901
152
Air Cooled Refrigeration Condensing Unit
Method of removed and replaced compressor in field
This system’s compressor has gas injection pipe. When you replace the compressor, you must
remove the piping fixture with gas injection pipe.
Please follow the procedure, replace the compressor.
Recommended tool for removed the screw
Ratchet socket wrench
Spanner
)
Tool
Expect the flat type
Only small size type
Only short-shank type
Gas injection
pipe
Suction
pipe
Discharge
pipe
Arrow view
Method removed piping fixture for gas injection pipe
(1) Insert the tool from behind the compressor, remove
the hexagon head screw (A) and tube fixture (C).On the
other screw (B), slacken it.
(2) Turn the piping fixture on a point of tube holder (D),
fold it toward.
(3) Cut the pipe for compressor with pipe-cutter.
M5 Hexagon
head screw (A)
Tube holder (C)
Piping fixture (stainless-steel)
Tube holder (D)
M5 Hexagon head screw (B)
View
Turn the
piping fixture
Cutting point
Tube holder (D)