Troubleshooting
SiENBE28-901
76
Air Cooled Refrigeration Condensing Unit
6.2
List of Malfunction Codes
No.
Item
Code
(Remote
control
display)
Detection
device
Criteria
Times
of
retry
LRMEQ5, 6AY1
LRLEQ5, 6AY1
LRMEQ8, 10, 12AY1
LRLEQ8, 10, 12AY1
LRMEQ15, 20AY1
LRLEQ15, 20AY1
Remarks
Level
Mal-
function
output
Output
during
backup
Level
Mal-
function
output
Output
during
backup
Level
Mal-
function
output
Output
during
backup
1
STD
compressor
OC
activation
E0
Current
sensor
14.95A
2
—
—
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
2
Earth
leakage
E2
• Leakage
breaker
• Earth leakage
breaker activates
within 20 seconds
after compressor
startup
0
Shutdown
—
ON
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
• Leakage
detector
PCB
• Leakage detector
PCB is activated
when HP<3.6MPa
3
Abnormal
high
pressure
level
E3
• High
pressure
switch
• 3.8MPa or more
0
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
• High
pressure
sensor
• 3.55MPa or more
3
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
5
—
—
—
Shutdown
ON
—
Alarm
—
ON
7
—
—
—
—
—
—
Shutdown
ON
—
4
Abnormal
low
pressure
level
E4
Low
pressure
sensor
SW5 is OFF
• 0MPa or less (MT)
• -0.015MPa or less (LT)
4
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
Refer to P.56 "(10) Low
pressure protection
control".
5
INV
compressor
lock
E5
Inverter
PCB
Position signal error
4
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
6
Outdoor fan
motor
malfunction
E7
Fan driver
PCB
Irregular fan motor
revolution
4
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
7
Electronic
expansion
valve
malfunction
E9
Main PCB
No continuity of
electronic expansion
valve coil
0
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
8
Abnormal
discharge
pipe
temperature
F3
Discharge
pipe
thermistor
• Discharge pipe temp.
>150°C
0
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
• Discharge pipe temp.
>120°C continuously
for 70 sec. or more
• Discharge pipe temp.
>125°C continuously
for 30 sec. or more
• Discharge pipe
temp.>130°C
14
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Discharge pipe temp.
>110°C, and
EV2_pls
≥
450 pls, and
EV3_pls
≥
450 pls
continuously for 60
sec.
3
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
5
—
—
—
Shutdown
ON
—
Alarm
—
ON
7
—
—
—
—
—
—
Shutdown
ON
—
9
3-sensor
malfunction
H0
Outdoor air
thermistor
Suction pipe
thermistor
Discharge pipe
thermistor
Heat exchanger
intermediate
inlet thermistor
Heat exchanger
intermediate
outlet thermistor
High pressure
sensor
Low pressure
sensor
When 3 or more
sensors detect
abnormality
0
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
10
High
pressure
switch
failure
H3
Main PCB
No continuity of high
pressure switch
0
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
11
INV
malfunction
L1
Inverter
PCB
Malfunction of IGBT or
INV is defected four
times in an hour
0
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
12
Radiating fin
temperature
rise
L4
Inverter
PCB
94°C
9
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
13
INV
compressor
instantaneo
us
overcurrent
L5
Inverter
PCB
9
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
14
INV
compressor
overcurrent
L8
Inverter
PCB
16.1A or more
9
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
15
Faulty INV
compressor
startup
failure
L9
Inverter
PCB
2
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
16
Transmission
failure between
control PCB and
inverter PCB
LC
Inverter
PCB
Transmission failure
between main PCB
and inverter PCB
No
limit
Alarm
—
ON
Alarm
—
ON
Alarm
—
ON
Automatic reset
17
INV
compressor
power voltage
imbalance
P1
Inverter
PCB
9
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"
18
Radiation fin
thermistor
P4
Inverter
PCB
Fin thermistor open
circuit or short circuit
No
limit
Alarm
—
ON
Alarm
—
ON
Alarm
—
ON
Automatic reset
19
Reversed
phase /
Open phase
U1
Main PCB
Reversed phase or
open phase
0
Shutdown
ON
—
Shutdown
ON
—
Shutdown
ON
—
Manual reset
"Reset the power supply"
20
INV
compressor
abnormal
power voltage
U2
Inverter
PCB
9
Shutdown
ON
—
Alarm
—
ON
Alarm
—
ON
Manual reset
"Reset the power supply"
or "Turn the operation
switch ON to OFF"