Troubleshooting
SiENBE28-901
90
Air Cooled Refrigeration Condensing Unit
6.6.4 “
E4
” Actuation of Low Pressure Sensor
Remote
Controller
Display
E4
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under compressor operation.
Low pressure <0.00MPa
Detected within 3 hours after power-on
Supposed
Causes
Abnormal drop of low pressure
Defect of low pressure sensor
Defect of outdoor unit PCB
Stop valve is not opened
Shortage of gas
Moisture choke