12 Unit installation
Installation and operation manual
12
LRYELRNUN5A7Y1
CO
₂
Conveni-Pack outdoor unit and capacity up unit
4P605461-1 – 2020.04
NOTICE
These units (LRYEN10* and LRNUN5*) are only parts of
an air conditioner system, complying with partial unit
requirements
of
the
International
Standard
IEC
60335-2-40:2018. As such, they must ONLY be connected
to other units that have been confirmed as complying to
corresponding partial unit requirements of this International
Standard.
General name and product name
In this manual, we use the following names:
General name
Product name
Outdoor unit
LRYEN10A7Y1
Capacity up unit
LRNUN5A7Y1
Temperature range
Refrigeration
A/C cooling
A/C heating
Outdoor
temperature
–20~43°C DB
–5~43°C DB
–20~16°C WB
Indoor
temperature
—
14~24°C WB
15~27°C DB
11.2
System layout
a
b
e
e
d
c
f
g
h
i
j
g
k
h
i
j
k
a
Main outdoor unit (LRYEN10*)
b
Capacity up unit (LRNUN5*)
c
Communication box (BRR9B1V1)
d
Fan (indoor unit for air conditioning)
e
Showcase (indoor unit for refrigeration)
f
Blower coil (indoor unit for refrigeration)
g
CO
2
control panel
h
CO
2
detector
i
CO
2
alarm
j
CO
2
ventilator
k
Shut off valve
11.3
Indoor unit constraints
NOTICE
The design pressure of the connected refrigeration parts
should be 9 MPa (90 bar) or more. If this is not the case,
please contact your dealer for assistance.
WARNING
Only the refrigeration parts that are also designed to work
with CO
2
shall be connected to the system.
Individual control with a remote controller
In case of a system with several air conditioners that are controlled
with the same remote controller in the same space:
Capacity class
Individual control with a
remote controller
50
NOT allowed
71~112
Allowed
Restrictions
Keep the following restrictions in mind when you connect indoor
units:
Restriction
Minimum/maximum
Minimum air conditioning total
capacity class
162
Maximum air conditioning total
capacity class
233
Maximum indoor units that can
be connected
≤4
For more information about the possible combinations, see the
installer and user reference guide of the outdoor unit.
12
Unit installation
12.1
Preparing the installation site
12.1.1
Installation site requirements of the
outdoor unit
Mind the spacing guidelines. See figure 1 on the inside of the front
cover.
Description of text on figure 1:
Item
Description
A
Maintenance space
B
Possible patterns with installation
spaces in case of a single
outdoor unit
(a)(b)(c)(d)
C
Possible patterns with installation
spaces in case of an outdoor unit
connected to a capacity up unit
(a)
(b)(c)(d)
h1
H1 (actual height) –1500 mm
h2
H2 (actual height) –500 mm
X
Front side = 500 mm + ≥h1/2
Y (for patterns B)
Air inlet side = 300 mm +≥h2/2
Y (for patterns C)
Air inlet side = 100 mm +≥h2/2
(a)
Wall height front side: ≤1500 mm.
(b)
Wall height air inlet side: ≤500 mm.
(c)
Wall height other sides: no limit.