12 Unit installation
Installation and operation manual
16
LRYELRNUN5A7Y1
CO
₂
Conveni-Pack outdoor unit and capacity up unit
4P605461-1 – 2020.04
Outdoor unit
Capacity up unit
▪ The preferred installation is on a solid longitudinal foundation
(steel beam frame or concrete). The foundation must be larger
than the grey marked area.
631
729
765
≥765
B
C
A
497
A
B
631
729
765
≥765
(mm)
1
2
Minimum foundation
1
LRYEN10*
2
LRNUN5*
Unit
A
B
C
LRYEN10*
1940
1102
193
Unit
A
B
C
LRNUN5*
635
497
—
▪ Fasten the unit in place using four foundation bolts M12. It is best
to screw in the foundation bolts until their length remains 20 mm
above the foundation surface.
20 mm
NOTICE
▪ Prepare a water drainage channel around the
foundation to drain waste water from around the unit.
When the outdoor temperatures are negative, the
drained water from the outdoor unit will freeze up. If the
water drainage is not taken care of, the area around
the unit might be very slippery.
▪ When installed in a corrosive environment, use a nut
with plastic washer (a) to protect the nut tightening part
from rust.
a
12.3.2
To install the outdoor unit
1
Transport the unit by crane or forklift and put it onto the
installation structure.
a
b
a
LRYEN10*
b
LRNUN5*
2
Fix the unit to the installation structure.