background image

14 Charging refrigerant

Installation and operation manual

24

LRYELRNUN5A7Y1

CO

 Conveni-Pack outdoor unit and capacity up unit

4P605461-1 – 2020.04

In case of remaining moisture

When the unit is installed on rainy days, moisture may still remain in
the piping after a first vacuum drying is performed. If so, conduct the
following procedure:

1

Pressurize  the  nitrogen  gas  up  to  0.05  MPa  (for  vacuum
destruction) and vacuum for at least 2 hours.

2

Afterwards, vacuum dry the unit to –0.1 MPa or less for at least
1 hour.

3

Repeat  vacuum  destruction  and  vacuum  drying  if  the  pressure
does not reach –0.1 MPa or less.

4

Leave the unit for more than 1 hour with a vacuum pressure of
–0.1 MPa or less. On the vacuum gauge, check if the pressure
does not increase.

13.5

Insulating the refrigerant piping

After  finishing  the  leak  test  and  vacuum  drying,  the  piping  must  be
insulated. Take into account the following points:

▪ Make sure to insulate the connection piping and refrigerant piping

branching entirely.

▪ Be sure to insulate the liquid and gas piping (for all units).

▪ Use  heat  resistant  polyethylene  foam  which  can  withstand  a

temperature of 70°C for:

▪ all  liquid  piping  at  both  the  air  conditioner  and  the  refrigeration

side.

▪ gas piping at the refrigeration side.

▪ Use  heat  resistant  polyethylene  foam  which  can  withstand  a

temperature of 120°C for gas piping at the air conditioner side.

Insulation thickness

Take  the  following  into  account  when  determining  the  insulation
thickness:

Piping

Mode

Minimum
temperature during
operation

Liquid piping

Refrigeration

0°C

Air conditioner

20°C

Gas piping

Refrigeration

–20°C

Air conditioner

0°C

Depending  on  your  local  weather  conditions,  you  may  need  to
increase  the  thickness  of  the  insulation.  If  the  ambient  temperature
exceeds 30°C and the humidity exceeds 80%.

▪ Increase the thickness of the liquid piping with ≥5 mm.

▪ Increase the thickness of the gas piping with ≥20 mm.

Insulation sealing

To  prevent  rain  and  condensed  water  entering  the  unit,  add  a
sealing between the insulation and the front panel of the unit.

a

a

a

a

b

b

a

Sealing material

b

Front panel

14

Charging refrigerant

14.1

Precautions when charging
refrigerant

CAUTION

A  vacuumed  system  will  be  under  triple  point.  Therefore,
ALWAYS  start  charging  with  R744  in  vapour  state.  When
the  triple  point  is  reached  (5.2  bar  absolute  pressure  or
4.2  bar  gauge  pressure),  you  may  continue  charging  with
R744 in liquid state.

INFORMATION

For  the  operation  method  of  the  stop  valves,  refer  to

"13.2 Using stop valves and service ports" 

[

4

 19].

WARNING

▪ Only  use  R744  (CO

2

)  as  refrigerant.  Other  substances

may cause explosions and accidents.

▪ When  installing,  charging  refrigerant,  maintaining  or

performing  service,  ALWAYS  use  personal  protective
equipment,  such  as  safety  shoes,  safety  gloves  and
safety glasses.

▪ If  the  unit  is  installed  indoors  (for  example,  in  a

machine room), ALWAYS use a portable CO

2

 detector.

▪ If  the  front  panel  is  open,  ALWAYS  beware  of  the

rotating  fan.  The  fan  will  continue  rotating  for  a  while,
even after the power switch has been turned off.

WARNING

The unit is already filled with a certain amount of R744. Do
NOT open liquid and gas stop valves until all checks from
the 

"17.2  Checklist  before  commissioning" 

[

4

  35]  are

completed.

CAUTION

Do  NOT  charge  liquid  refrigerant  directly  from  a  gas  line.
Liquid  compression  could  cause  compressor  operation
failure.

NOTICE

If  the  power  of  some  units  is  turned  off,  the  charging
procedure cannot be finished properly.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

NOTICE

Before  starting  charging  procedures,  check  if  the  7‑LEDs
display  is  as  normal  (see 

"16.1.4  To  access  mode  1  or

2" 

[

4

  34]).  If  a  malfunction  code  is  present,  see

"18.1 Solving problems based on error codes" 

[

4

 37].

NOTICE

Close  the  front  panel  before  any  refrigerant  charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.

Summary of Contents for LRYEN10A7Y1

Page 1: ...Installation and operation manual CO Conveni Pack outdoor unit and capacity up unit English Installation and operation manual CO Conveni Pack outdoor unit and capacity up unit LRYEN10A7Y1 LRNUN5A7Y1...

Page 2: ...mm 300 500 500 10 B B1 B2 B3 100 500 500 50 300 200 a a C1 C2 C3 C a 300 500 20 10 50 100 500 100 300 400 200 a A Y X h2 H2 500 h1 H1 1500 1...

Page 3: ...and service ports 19 13 2 1 To handle the stop valve 19 13 2 2 To handle the service port 20 13 2 3 Tightening torques 21 13 3 Connecting the refrigerant piping 21 13 3 1 To remove the spun pipes 21...

Page 4: ...from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable standard I...

Page 5: ...tar system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce perform...

Page 6: ...bol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this chemical symbol means that the battery contains a heavy metal a...

Page 7: ...e executing any maintenance task WARNING Never replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or...

Page 8: ...instruments or works of art NOTICE Do NOT use the system for cooling water It may freeze NOTICE For future modifications or expansions of your system A full overview of allowable combinations for futu...

Page 9: ...Phase diagram of R744 P bar T C 0 31 100 80 1 5 2 73 8 57 d c b a e P Pressure in bar T Temperature in C a Solid phase b Liquid phase c Vapour phase d Supercritical fluid e Triple point 57 C 5 2 bar 6...

Page 10: ...ge Restart the unit by switching operating switch OFF and ON If the problem persists refer to the service manual The stop valve of an outdoor unit is left closed Open the stop valve on both the gas an...

Page 11: ...unit a b a Outdoor unit b Capacity up unit NOTICE Use a belt sling of 20 mm wide that adequately bears the weight of the unit Forklift a b a Outdoor unit b Capacity up unit NOTICE Use filler cloth on...

Page 12: ...your dealer for assistance WARNING Only the refrigeration parts that are also designed to work with CO2 shall be connected to the system Individual control with a remote controller In case of a system...

Page 13: ...alculations see the reference guide of the indoor unit Appropriate measures INFORMATION Appropriate measures are field supply Choose and install all required appropriate measures in accordance with EN...

Page 14: ...echanical ventilation in accordance with EN 378 3 2016 12 2 Opening and closing the unit 12 2 1 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING To gain access to...

Page 15: ...it b Capacity up unit 3 Attach the small front plates to the front panels a b 2 7 a Outdoor unit b Capacity up unit 12 3 Mounting the outdoor unit 12 3 1 To provide the installation structure Make sur...

Page 16: ...n bolts M12 It is best to screw in the foundation bolts until their length remains 20 mm above the foundation surface 20 mm NOTICE Prepare a water drainage channel around the foundation to drain waste...

Page 17: ...ion 13 1 2 Refrigerant piping material Piping material K65 copper iron alloy CuFe2P maximum operating pressure 120 bar Piping temper grade and thickness Piping refrigeration unit Piping type Outer dia...

Page 18: ...easily a c b a Showcase b Height difference 5 m c Trap The refrigerant suction piping must always run down a b a b a Outdoor unit or indoor unit b Flow direction in refrigerant suction piping To inst...

Page 19: ...15 9 t1 05 K65 Air conditioner side liquid pipe b 12 7 t0 85 K65 Air conditioner side gas pipe b 15 9 t1 05 K65 a Piping between branching areas C D c d b Piping from first branch to second branch B2...

Page 20: ...te and freeze between the screw thread As a result refrigerant may leak and the valve cap may break a b a Apply screw lock agent b Do NOT apply screw lock agent 5 Tighten the valve cap Also see 13 2 3...

Page 21: ...ese instructions are NOT followed correctly it may result in property damage or personal injury which may be serious depending on the circumstances To remove the spun piping 1 Open the stop valve cap...

Page 22: ...p valve gas refrigeration B Stop valve liquid refrigeration a Gas piping b Liquid piping 2 If applicable remove the knockout and connect the piping to the capacity up unit Side connection 3 Remove the...

Page 23: ...to withstand high pressures and which will prevent water dirt or dust entering the unit CAUTION Do NOT open the stop valve until you have measured the insulation resistance of the main power supply ci...

Page 24: ...th 20 mm Insulation sealing To prevent rain and condensed water entering the unit add a sealing between the insulation and the front panel of the unit a a a a b b a Sealing material b Front panel 14 C...

Page 25: ...4 the additional amount of refrigerant during test run 6 and the factory charged amount of refrigerant 5 see label on the unit The total amount of refrigerant in the system is thus 4 5 6 7 10 Note do...

Page 26: ...kg 5 Factory charged amount of refrigerant into outdoor unit kg 6 3 6 Additional amount of refrigerant charged when test run if required kg a 7 Total amount of refrigerant 5 6 7 kg 8 a The maximum amo...

Page 27: ...consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax EN IEC 61000 3 12 provided tha...

Page 28: ...d1 d2 h h1 h2 d1 d2 X1M A1P X5M X4M X1M PE X1M X3M PE X1M A1P X2M X1M X3M PE k1 k l m k2 k4 k3 j 3N 50 Hz 380 415 V AC c1 c2 3N 50 Hz 380 415 V AC c1 c2 c1 c2 1N 50 Hz 220 240 V AC c1 c2 k5 a Capacity...

Page 29: ...b X5M X4M X1M PE X1M A1P X2M X1M X3M PE a Terminals on outdoor unit b Terminals on capacity up unit Terminal Screw size Tightening torque N m X1M Power supply M8 5 5 7 3 PE Protective earth screw M8...

Page 30: ...fixing b F2 F1 F1 X1M A1P c a F2 Q1 Q2 TO MULTIUNIT TO OUT DUNIT TO IN DUNIT d e 2 1 3 X5M a b c d e X1M A1P X5M 1 2 X1M A1P DIII transmission wiring a To capacity up unit b To indoor units air condit...

Page 31: ...rror occurs that causes unit operation to stop R P2 run signal connection optional when the compressor is running P1 P2 operation signal connection mandatory when the expansion valves of the connected...

Page 32: ...on of the capacity up unit a remote operation switch is required Use a voltage free contact for microcurrent 1 mA 12 V DC Connect to X3M 1 2 and set to Remote R E M O T E OFF O N S1S S1S Factory equip...

Page 33: ...ain PCB A1P of the outdoor unit and capacity up unit This involves the following field setting components Push buttons to give input to the PCB A 7 segment display to read feedback from the PCB DIP sw...

Page 34: ...lay goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have power runni...

Page 35: ...side of the unit on refrigerant leakage If there is a refrigerant leak try to repair the leak If the repair is unsuccessful call your local dealer Do not touch any refrigerant which has leaked out fro...

Page 36: ...s and circuit breakers on the indoor unit PCB did not trip Operation parameters For a stable operation of the unit each of the following parameters should be in its range Parameter Range Root cause wh...

Page 37: ...the maintenance and repair works Quantities and kind of new reused recycled reclaimed refrigerant which have been charged on each occasion Quantities of refrigerant which have been transferred from th...

Page 38: ...downstream of indoor units error displayed on remote controller O Wrong combination of indoor units Check the number of connected indoor units Check if an indoor unit is installed that is not a possib...

Page 39: ...ata is available on the Daikin Business Portal authentication required 19 1 Piping diagram Outdoor unit HPS HPS HPS os L M H L SV RV M 15 9 C1220T H 15 9 C1220T H 15 9 C1220T H 19 1 C1220T H M M M Pre...

Page 40: ...19 2 Piping diagram Capacity up unit 15 9 C1220T H 15 9 C1220T H L RV M M HPS os H Pressure sensor Plate heat exchanger HPS Pressure switch Heat exchanger Check valve os Oil separator Service port RV...

Page 41: ...ted circuit board earth leakage detector E1HC Crankcase heater M1C E2HC Crankcase heater M2C E3HC Crankcase heater M3C L1R Reactor A3P L2R Reactor A4P L3R Reactor A5P M1C Motor compressor INV1 M2C Mot...

Page 42: ...Crankcase heater M1C F1U F2U Fuse T 6 3 A 250 V A1P F1U Fuse A6P F101U Fuse A4P F3U F4U Fuse B 1 A 250 V F401U F403U Fuse A3P F601U Fuse A2P HAP Light emitting diode service monitor is green A1P A2P...

Page 43: ......

Page 44: ...4P605461 1 2020 04 Copyright 2020 Daikin 4P605461 1 0000000K Verantwortung f r Energie und Umwelt...

Reviews: