4-19
4.8.8 High Pressure Switch (HPS)
Type
ACB-LB164
Setting value
OFF 2400kPa
(
24.47kg/cm
2
)
ON 1900kPa
(
19.37kg/cm
2
)
●
Replacement method
1. Remove cable from inverter box.
2. Remove HPS from joint with check valve.
※
Loosen flare nuts A and B using two wrenches.
(Fig. 1)
※
Do not lose push-stick inside the joint. (Fig. 2)
3. Installing of HPS
※
Tighten flare nuts A and B using two wrenches.
(Fig. 1)
4. Make sure no gas leakage after install HPS.
4.8.9 High Pressure Sensor (HPT)
Type
NSK-BD030F-070
●
Removal of HPT
1. Remove HPT cable from control box.
2. Remove heat shrink tube and HPT from joint with
check valve.
※
Loosen flare nuts A and B using two wrenches.
(Fig. 1)
※
Do not lose push pin inside the joint with check
valve. (Fig. 2)
●
Installing of HPT
1. Insert heat shrink tube into HPT body.
2. Connect HPT to joint with check valve.
※
Tighten flare nuts A and B using two wrenches.
(Fig. 1)
3. Conduct gas leakage test and check to make
sure no gas leakage after installing of HPT.
4. Set one end of heat shrink tube to joint seat with
check valve (Fig. 3) and then
①
Shrink the tube by heating up using hair dryer.
(Fig. 3)
②
Apply silicon sealant to both ends inside of
the tube. (Fig. 3)
③
Band both ends of the tube. (Fig. 3)
④
Bend HPT cable and band the cable to HPT
body. (Fig. 4)
Fig. 1 Use two wrenches when
removing and installing.
B
Joint with check valve
HPS
(
or HPT
)
A
Two wrenches
Discharge pipe
Fig. 2 Do not loss push-stick.
Joint with check valve
Push-stick
④
Band the cable to
HPT body
Fig. 4
③
Band both ends of the tube.
Heat shrink tube
②
Apply silicon sealant to
both ends inside of the tube
Fig. 3
Joint seat with check valve
①
Shr
ink the
tube in this area
HPT
04̲01-26̲LX10F11B̲En.indd 4-19
04̲01-26̲LX10F11B̲En.indd 4-19
2014/11/19 16:42:24
2014/11/19 16:42:24
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...