4-23
4.8.15 Check Valve
●
Replacement method
1. Refer location of check valves to below picture.
2. Do not make any mistake about the installation
direction (arrow direction) of the check valve
3. While brazing, keep valve cool below 120
℃
(248 F) with wet cloth.
4. Check if there is no gas leakage after completion
of brazing.
4.8.16 Filter and Strainer
●
Replacement method
1. Refer location of check valves to below picture.
2. Install the new check valve in the direction which
an arrow shows.
3. Check if there is no gas leakage after completion
of brazing.
⑥⑦
Strainer
④⑤
Filter
①
Check valve (Spring type)
②③
Check valve (No spring type)
Valve chamber
Economizer
Reheat coil (option)
Receiver
Compressor
HPT
HPS
EMV
ESV
LSV
Dryer
EEV
LPT
Sight glass
CFM
EFM
RSV
HSV
PRV
DMV
⑦
①
⑤
⑥
Evaporator
Condenser
③
②
④
Name
No.
Size
Application
Check valve
①
5/8 ,
φ
15.9
DMV outlet
②③
3/8 ,
φ
9.5
HSV, RSV outlet
Filter
④
1-1/4 , 31.8
φ
Compressor inlet
⑤
1/2 , 12.7
φ
LSV, ESV inlet
Strainer
⑥
5/8 , 15.9
φ
DMV, HSV, RSV inlet
⑦
1/2 , 12.7
φ
EEV inlet
04̲01-26̲LX10F11B̲En.indd 4-23
04̲01-26̲LX10F11B̲En.indd 4-23
2014/11/19 16:42:29
2014/11/19 16:42:29
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...