5-2
5.1 Standard Tightening Torque for Bolt and Flare Nut
Type
Size
Tightening Torque
Example of Application
N
・
m
kgf
・
m
lbf
・
ft
Bolt
M4
1.6
16
1.2
Small parts
M5
3.0
30
2.3
Solenoid valve
Inverter box cover
M6
5.2
51
3.8
Slide plate for EFM stator
Condenser fan grille
Solenoid valve chamber cover
M8
12.3
121
9.1
Fixing plate of evaporator fan diffuser
Condenser fan motor
Control box door
Access panel
M10
25.2
247
18.6
M12
42.7
418
31.5
Compressor base
M14
Reverse threaded
67.8
664
50.0
Evaporator fan shaft
Flare nut
φ
6.4, 1/4
15.7
154
11.6
Low-pressure port
φ
9.5, 3/8
36.3
356
26.8
φ
12.7, 1/2
54.9
538
40.5
Dryer, Compressor injection port
Compressor
connector
(φ
19.1 , 3/4
)
122
1200
90
Compressor suction and discharge
05̲01-08̲LX10F11B̲En.indd 5-2