1-10
1.3.8 Printed Circuit Board
●
CPU Board
(
EC1
)
Controller described in this manual as CPU board.
CPU board equips micro-computer and controls
unit with operation software installed.
All information required for the control is input to
the CPU board.
①
Sensor information (temperature, humidity,
pressure) and power information (voltage, phase
sequence, current) are input.
②
Configuration items (factory set) in accordance
with requirement for individual user's order are
input.
③
For example Unit ON/OFF, SP change, etc are
inputted by key operation.
In responding to these inputs, CPU board outputs
commands to each part to operate unit with
accuracy.
①
to modulation valves, solenoid valves and
magnetic contactors
②
to inverter board
③
to LCD display
Operation data is stored for 2 years
(
Logging
interval 60 minutes). The data can be downloaded
using a PC which has the DCCS software installed
or with a USB memory.
When power OFF, some of setting work and data
indication can be available by wake-up battery
power (Rechargeable battery). Data download and
software upload are also possible. (Refer battery
mode in paragraph 2.3)
Use Daikin spare parts for CPU board replacement.
After replacement, configuration items are
transmitted from operation board. Set controller
time in accordance with setting request displayed
on LCD. Install the latest operation software down-
loaded from web site.
●
I/O Board
(
EC2
)
I/O board converts AC24V power from control
transformer Tr1 to DC13V/DC5V and supply it to
CPU board.
I/O board energizes magnetic contactors for fan
motor EFM, CFM and phase correction contactor
PCC1 or 2 by receiving order from CPU board.
At the same time, LED lamps wired in parallel
with them are energized and lighted ON. That is
convenience with service work.
●
Operation Board
(
EC3
)
Operation board receives input from keyboard and
transmits it to LCD board and CPU board. On the
other hand it transmits signals from CPU board to
LCD board.
If communication between operation board and
CPU board is failed, operation board judges to
display "Communication Interrupted" on LCD and
alarm E903 is shown on trip report.
Configuration items factory set to CPU board have
been copied to operation board. When CPU board is
replaced, these items are transmitted to CPU board.
●
Inverter Board
(
EC8
)
Inverter board changes frequency of power source
and controls compressor speed. Inverter board
receives command of rotation speed value from
CPU board. The operating condition during inverter
control (compressor overload, power supply
condition and actual frequency etc.) are transmitted
to CPU board. The judgment for operation
continuing and stopping is conducted by CPU board.
Output from inverter is made of frequent switching
control by power module and results to creating
high temperature. Radiator fin constructed outside
inverter box.
CFM
EFM
PT/CT
EC7
Operation board
EC3
Inverter box
Control box
CB
Compressor
AC24V
3 phase AC
380-415V/50Hz
440-460V/60Hz
CM
Inverter board
EC8
ACL
Noise filter
board EC9
Sheet key
EC6
LCD
EC4
I/O board
EC2
CPU board
EC1
Fan motors
SV
EEV EMV DMV
Sensors
Modulation Valves
Solenoid Valves
Input to
CPU board
Output from
CPU board
AC
⇒
DC
⇒
Inverter control
Tr1
01̲01-22̲LX10F11B̲En.indd 1-10
01̲01-22̲LX10F11B̲En.indd 1-10
2014/11/19 16:40:25
2014/11/19 16:40:25
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...