1-19
1.5.3 ACT, Automatic Cold Treatment
●
ACT operation
When cold treatment is completed during USDA
transport (when the standard period has passed
with the standard pulp temperature kept equal to
or less than the base temperature), ACT function
switches the temperature to the preset temperature
automatically to continue the operation.
To activate ACT, the following 4 items must be set.
1. Cold treatment period CT (day)
2. Maximum pulp temperature US-Max (
℃)
3. Set temperature during cold treatment SP (
℃
)
4. Set temperature after cold treatment is
completed End-SP (
℃
)
ACT operation starts
SP
US-Max
CT
*1 Timer CT count starts
* 5
* 3
End-SP
Cold treatment
*2 * 4
* 4
Supply air temperature sensor
(Control sensor SS)
USDA sensor temperature
*1 When all USDA sensor temperature has dropped
lower than US-Max, CT-day starts to count.
*2 When the temperature exceeds US-Max during
cold treatment, which results in data logged, CT
counting is cancelled. When the temperature
dropped lower than US-Max, again, counting
starts to recount cold treatment days (CT day).
*3 After cold treatment is completed, the operation
starts at End-SP setting temperature.
*4 SP and End-SP can be changed during ACT
operation (CT day and US-Max can not be
changed)
*5 The temperature is raised gradually (0.1
℃
per
hour) to prevent rapid temperature rise.)
●
Access to ACT operation
Access to
※
2-6 ACT setting in paragraph 2.3.
●
Indications during ACT operation
During USDA operation, ACT is displayed in the
SET-MODE area.
The SET-MODE area will change to USDA INFO
every 5 seconds, and the current USDA sensor
value will be displayed. (Figure below)
CHILLED
HP : 1200kPa
LP : 20kPa
MODULATION
-1.0
˚
C
DEF-INT AUTO
RETURN 1.7
℃
SET POINT
SUPPLY
-
1.1
˚
C
Automatically
switches
every 5
seconds
SET- MODE
USDA
ACT
CHILLED
HP : 1200kPa
LP : 20kPa
MODULATION
-1.0
˚
C
DEF- INT AUTO
RETURN 1.7
℃
SET POINT
SUPPLY
-1.1
˚
C
USDA Info.
Automatic Cold Treatment
SP
- 1.0
℃
US-Max 1.5
℃
End SP 2.0
℃
CT Total 25Day
USDA1
-0.8
℃
USDA2
ERROR
USDA2 -0.6
℃
CTS N/A
Current -1.0
℃
SP
Remain 10Day20Hr
Status ACTIVE
Operation screen
ACT screen
USDA1 -0.8
℃
USDA2 ERROR
USDA3 -0.6
℃
CTS N/A
When the or key is
pressed, the ACT setting status
and the current operating status
can be checked.
●
Cancellation of ACT operation
1. Cancellation of ACT operation
1) When ACT is set to "OFF"
2) When F-PTI is completed
3) When Chilled PTI is completed
4) When Frozen PTI is completed
2. Power off (unit off) during ACT operation and
operations when restarting
Stop time
ACT operation when restarting
Less than 1 hour ACT continues
1 hour or more to
less than 48 hours
CT counting is reset and ACT
restarts
48 hours or more to
less than 72 hours
ACT continues with End-SP.
72 hours or more ACT cancelled
01̲01-22̲LX10F11B̲En.indd 1-19
01̲01-22̲LX10F11B̲En.indd 1-19
2014/11/19 16:40:34
2014/11/19 16:40:34
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...