2-24
003
F301
・
E303
・
E305
・
E307
・
E311
Alarm
Logic
and
Possible
Causes
①
After both CPU board (EC1) and operation board (EC3) are replaced together, the initial
setup is not executed.
②
E307, E311--- After CPU board (EC1) is replaced, the configuration set is not executed.
③
E307, E311---No power supply to S-RAM (CPU board) during power off due to CPU onboard
battery (CPU board) failure. (E801 is also generated.)
Trouble
Shooting
①
,
②
Set configuration setting
F301 Temperature setting request
--- Set temperature, following
*
1 Set Point Change in paragraph 2.3 (Set Point
temperature Change).
E303 Humidity setting request
--- Set humidity, following
*
2-3 Humidity Setpoint in paragraph 2.3.
E305 Defrost Interval setting request
--- Set defrost interval, following
*
2-1 Defrost Interval in paragraph 2.3.
E307 Calendar setting request
--- Set
*
12-11 Controller date (year/month/day) and
*
12-12 Controller time (time), referring
*
12 Configuration Set in paragraph 2.3.
E311 Trip start setting requirement
--- Set *20 Trip Start Time to "0" (press ENTER key for three seconds.), referring Manual
Check in paragraph 4.1.
③
Permanent measures
○
If E801 is also generated, replace CPU board.
Emergency measures
○
The unit will operate, However, controller time starts from incorrect time whenever power
OFF/ON. therefore, trip data may not shown correctly.
Controller
Action
F301
Unit stop
E303
Alarm display only.
E305
Alarm display only.
E307
Alarm display only.
E311
Alarm display only.
02̲19-44̲LX10F11B̲En.indd 2-24
02̲19-44̲LX10F11B̲En.indd 2-24
2014/11/19 16:37:57
2014/11/19 16:37:57
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...