2-41
102
F52E
・
F52F
・
F53B
E52D
・
E52E
・
E52F
Alarm
Logic
&
Possible
Causes
Alarm Logic
Possible Causes
E52D
:
Fin temperature sensor failure
Inverter board failure
(
Fin temperature sensor
)
(
Fin temperature
≧
150
℃
or -45
≦℃)
F52E
:
E52E is generated 4 times.
E52E
:
Over current failure
Inverter board failure
(
IPM part
)
IPM
:
Intelligent Power Module
F52F
:
E52F is generated 4 times.
E52F
:
Compressor current sensor failure
Inverter board failure
(
Current detection part
)
F53B
:
EEPROM failure when unit is on
Inverter board failure (EEPROM part)
EEPROM : Electrically Erasable Program ROM
Trouble
Shooting
Replace Inverter board
Controller
Action
F52E, F52F, F53B
Unit stop
E52D
Restart after 3 minutes
E52E, E52F
Restart after 3 minutes (F52E, F52F is generated at 4 times retry.
)
02̲19-44̲LX10F11B̲En.indd 2-41
02̲19-44̲LX10F11B̲En.indd 2-41
2014/11/19 16:38:12
2014/11/19 16:38:12
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...