1-3
1.2 Set Point and Protection Device
Component Name
Detector Symbol
Setting Value
Alarm
High pressure switch
HPS
OFF
≧
2400kPa
(
24.47kg/cm
2
)
ON
≦
1900kPa
(
19.37kg/cm
2
)
E101
F101
Pressure relief valve
PRV
Open
≧
2450kPa
(
25.0kg/cm
2
)
−
Fusible plug
−
95
〜
100
℃(
203
〜
212
℉)
−
Built-in thermal protector
for condenser fan motor
Q1M
OFF
≧
135
℃±
5
℃(
275
℉±
41
℉)
ON
≦
86
℃±
15
℃(
187
℉±
59
℉)
−
Built-in thermal protector
for evaporator fan motor
−
OFF
≧
145
℃±
5
℃(
293
℉±
41
℉)
ON
≦
94
℃±
15
℃(
201
℉±
59
℉)
−
Circuit breaker (ELCB)
CB
30A
(
100mA
)
−
●
Fuse and Protection Circuit
Board
Fuse
Type
Protection Circuit
Alarm
I/O board
(
EC2
)
F1U
F10A 250V
fast-acting type
I/O board control power
(
DC13.5V, 5V, 3.3V
)
−
F2U
PCC1, PCC2, CFH, CFL, EFH, EFL
HSV, RSV, LSV, ESV
F703
F707
E115
E117
F3U Spare
−
PT/CT
board
(
EC7
)
F11U
8A 600V
PT/CT board control power
−
Noise filter
board
(
EC9
)
F5U
12.5A 300A
Surge absorber 1 (lightning surge protection)
<Non-replaceable>
−
F6U
Surge absorber 2 (lightning surge protection)
<Non-replaceable>
−
F7U
Surge absorber 3 (lightning surge protection)
<Non-replaceable>
−
F8U
8A 600V
Inverter control circuit <Non-replaceable>
−
I/O board
(
EC2
)
TH3
2.5A 72V
Automatic reset
RM (Remote Monitoring) circuit
<Non-replaceable>
−
TH2
TransFresh circuit <Non-replaceable>
−
01̲01-22̲LX10F11B̲En.indd 1-3
01̲01-22̲LX10F11B̲En.indd 1-3
2014/11/19 16:40:19
2014/11/19 16:40:19
https://daikin-p.ru
Summary of Contents for LX10F11B
Page 2: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...
Page 6: ...https daikin p ru...
Page 82: ...https daikin p ru...
Page 92: ...https daikin p ru...
Page 127: ...5 9 5 6 Sequence https daikin p ru...
Page 128: ...5 10 Stereoscopic wiring diagram https daikin p ru...
Page 129: ...Revision A Correction of spelling 2012 9 28 https daikin p ru...