4-8
4.4 Checking Non-Condensable Gas
If the air or other non-condensable gases are
present in the refrigerant system, they will gather
in the condenser and the pressure inside the
condenser will rise significantly.
In this case, recover all refrigerant and charge the
specified charge amount of refrigerant.
Confirm whether the air or other non-condensable
gas is present with following procedure.
(1) Collect refrigerant to condenser coil and
receiver by operating automatic pumpdown.
(2) Operate condenser fan using CFM ON/OFF
function in manual check and wait until the
air inlet and outlet temperature of condenser
becomes equal.
(3) Connect manifold gauges (High pressure
gauge) to port
④
.
Non-condensable gas are present if the
corresponding saturation temperature of gauge
pressure is higher than the temperature of the
outdoor air.
4.5 Sight Glass
Sight glass shows moisture content in the refrigerant
and refrigerant flow rate.
Sight
Glass
(1) Moisture indication
Recover all refrigerant and recharge new
refrigerant if the sight glass indicates yellow as
excessive moisture may be contained in the
system.
Green
Dry
Yellow
Wet
Color
Judgment
(2) Judgment for refrigerant flow rate, Normal or
Shortage?
Judge refrigerant flow rate when frozen mode only
under 0
℃
.
Normal if full is indicated at RS < 0
℃
.
Shortage if flashing is indicated at RS < 0
℃
.
RS
<
0
℃
RS
<
0
℃
Normal
Shortage
Judgment
Frozen Operation
Flashing
Full
CAUTION
Do not judge shortage if flashing is
indicated at RS > 0
℃
frozen mode and at
any range of chilled mode.
As flashing here does not mean gas
shortage, do not charge with additional
refrigerant.
It is possibly caused by overcharging.
04章̲LX10F11B3̲TR16-02̲En.indd 4-8
04章̲LX10F11B3̲TR16-02̲En.indd 4-8
2016/02/03 16:22:02
2016/02/03 16:22:02
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...