5-3
5.2 Protective Device and Setpoints
Component Name
Detector Symbol
Setting Value
Alarm
High pressure switch
HPS
OFF
≧
2400kPa
(
24.47kg/cm
2
)
ON
≦
1900kPa
(
19.37kg/cm
2
)
E101
F101
Pressure relief valve
PRV
Open
≧
2450kPa
(
25.0kg/cm
2
)
−
Fusible plug
−
95
〜
100
℃(
203
〜
212
℉)
−
Built-in thermal protector
for condenser fan motor
Q1M
OFF
≧
135
℃±
5
℃(
275
℉±
41
℉)
ON
≦
86
℃±
15
℃(
187
℉±
59
℉)
−
Built-in thermal protector
for evaporator fan motor
−
OFF
≧
145
℃±
5
℃(
293
℉±
41
℉)
ON
≦
94
℃±
15
℃(
201
℉±
59
℉)
−
Circuit breaker (ELCB)
CB
30A
(
100mA
)
−
Cooling Water Pressure Switch
WPS
OFF
≧
98kPa
(
1.0kg/cm
2
)
ON
≦
39kPa
(
0.4kg/cm
2
)
−