5-7
5.6 Parts Replacement
5.6.1 Cooling Water Pressure Switch
(WPS)
●
Type LCB-MB10
●
Setpoint OFF 98kPa
(1.0kg/cm
2
)
ON
39kPa
(0.4kg/cm
2
)
●
This is used to switch between air-cooled
operation and water-cooled operation. The
cooling water flows, and when the inlet water
pressure reaches the setpoint, the contact
switches OFF, the condenser fan is stopped, and
water-cooled operation is performed.
(1) Replacement procedure
①
Remove the WPS lead wire from the controller
terminal block.
②
Stop the cooling water pump, check that no
water pressure is being applied, and then
remove the WPS.
③
Replace the WPS, apply seal tape around the
threads, and then tighten the screw.
①
Cooling Water Pressure Switch (WPS)
②
Cooling water inlet joint
③
Cooling water outlet joint
④
Inlet joint cap
⑤
Outlet joint cap
⑤
④
③
②
①
05章̲LX10F11B3̲TR16-02̲En.indd 5-7
05章̲LX10F11B3̲TR16-02̲En.indd 5-7
2016/02/02 9:54:29
2016/02/02 9:54:29