6-2
6.1 Standard Tightening Torque for Bolt and Flare Nut
Type
Size
Tightening Torque
Example of Application
N
・
m
kgf
・
cm
Ibf
・
ft
Bolt
M4
1.6
16.3
1.2
Small parts
M5
3.0
30.6
2.2
Solenoid valve
M6
5.2
53.0
3.8
Evaporator fan Stator slide plate
Condenser fan grille
Valve chamber cover
M8
12.3
125.4
9.1
Evaporator fan Stator fixing plate
Condenser fan motor
Control box door
Access panel
M10
25.2
257.0
18.6
M12
42.7
435.4
31.5
Compressor Base
M14
Reverse threaded
67.8
691.4
50.0
Evaporator fan shaft
Flare nut
φ
6.4, 1/4
15.7
169.1
11.6
Low-pressure port
φ
9.5, 3/8
36.3
370.2
26.8
φ
12.7, 1/2
54.9
559.8
40.5
Dryer, Compressor injection port
Compressor
connector
(φ
19.1, 3/4
)
122
1244.1
90.0
Compressor suction and discharge
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-2
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-2
2016/01/28 9:24:14
2016/01/28 9:24:14
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...