6-5
●
NTC type USDA Sensor Characteristics, USDA1, USDA2, USDA3, CTS (Option)
Set sensor type "2" in
※
12 Configuration Set
in paragraph 2.3 for NTC type USDA sensor.
Temperature
(℃)
Temperature
(
F
)
Resistance
(
k
Ω)
Temperature
(℃)
Temperature
(
F
)
Resistance
(
k
Ω)
−
20
−
4
97.391
10
50
19.893
−
19
−
2
91.883
11
52
18.964
−
18
0
86.721
12
54
18.083
−
17
1
81.882
13
55
17.249
−
16
3
77.343
14
57
16.457
−
15
5
73.034
15
59
15.709
−
14
7
69.087
16
61
14.995
−
13
9
65.333
17
63
14.320
−
12
10
61.805
18
64
13.678
−
11
12
58.491
19
66
13.069
−
10
14
55.379
20
68
12.491
−
9
16
62.442
21
70
11.041
−
8
18
49.684
22
72
11.419
−
7
19
47.087
23
73
10.922
−
6
21
44.641
24
75
10.450
−
5
23
42.338
25
77
10.001
−
4
25
40.167
26
79
8.574
−
3
27
38.120
27
81
8.157
−
2
28
36.190
28
82
8.779
−
1
30
34.369
29
84
8.411
0
32
32.651
30
86
8.060
1
34
31.028
31
88
7.725
2
36
29.494
32
90
7.406
3
37
28.047
33
91
7.102
4
39
25.678
34
93
6.812
5
41
25.385
35
95
6.535
6
43
24.162
36
97
6.271
7
45
23.005
37
99
6.200
8
46
21.910
38
100
5.779
9
48
20.874
39
102
5.550
3P156427A
Receptacle for
NTC
setting "2"
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-5
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-5
2016/01/28 9:24:14
2016/01/28 9:24:14
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...