6-6
●
ST9702-1 type USDA Sensor Characteristics, USDA1, USDA2, USDA3,
CTS (Option)
Set sensor type "1" in
※
12 Configuration Set
in paragraph 2.3 for ST9702-1 type USDA
sensor.
Temperature
(℃)
Temperature
(
F
)
Resistance
(
k
Ω)
Temperature
(℃)
Temperature
(
F
)
Resistance
(
k
Ω)
−
20
−
4
36.240
10
50
9.196
−
19
−
2
34.470
11
52
8.821
−
18
0
32.800
12
54
8.465
−
17
1
31.220
13
55
8.124
−
16
3
29.720
14
57
7.800
−
15
5
28.310
15
59
7.490
−
14
7
26.970
16
61
7.194
−
13
9
25.710
17
63
6.911
−
12
10
24.510
18
64
6.641
−
11
12
23.370
19
66
6.383
−
10
14
22.290
20
68
6.136
−
9
16
21.270
21
70
5.901
−
8
18
20.300
22
72
5.675
−
7
19
19.380
23
73
6.460
−
6
21
18.510
24
75
5.253
−
5
23
17.680
25
77
5.056
−
4
25
16.900
26
79
4.867
−
3
27
16.150
27
81
4.685
−
2
28
15.440
28
82
4.513
−
1
30
14.770
29
84
4.348
0
32
14.120
30
86
4.189
1
34
13.520
31
88
4.036
2
36
12.940
32
90
3.891
3
37
12.380
33
91
3.751
4
39
11.860
34
93
3.617
5
41
11.360
35
95
3.488
6
43
10.880
36
97
3.365
7
45
10.430
37
99
3.247
8
46
9.999
38
100
3.133
9
48
9.588
39
102
3.024
10
50
9.196
40
104
2.919
AD970217A
Receptacle for
ST9702-1
setting "1"
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-6
06章01-08̲LX10F11B3̲TR16-02̲En.indd 6-6
2016/01/28 9:24:14
2016/01/28 9:24:14
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...