2-20
●
E Alarm
Diagnosis
Alarm
code
Alarm content
Controller action
001
E101
HPS activates during operation
Restart after 3 min.
101
E105
Compressor operating current is too high (over DC 51A)
Restart after 3 min.
030
E106
Abnormal compressor operation
Restart after 3 min.
002
E107
DCHS1 or DCHS2 becomes 130
℃
or more for 10 minutes or 145
℃
or more.
Restart after 3 min.
002
E109
LPT drops below -70kPa during operation
Restart after 3 min.
010
E115
Condenser fan motor internal thermostat activated
Restart after 3 min.
011
E201
Pumpdown control is not completed within rated time
Alarm display only
012
E202
Automatic pumpdown failure
Alarm display only
013
E203
Overcooling prevention
Restart after 3 min.
014
E207
Defrost is not completed in 90 min.
Alarm display only
003
E303
Humidity setting request (during dehumidification operation)
Alarm display only
015
E304
Incorrect configuration set (Reheat coil)
Alarm display only
003
E305
Defrost interval setting request
Alarm display only
003
E307
Calendar setting request
Alarm display only
003
E311
Trip start setting request
Alarm display only
016
E401
Supply air temperature sensor (SS) failure
Backup operation
016
E402
Data recorder supply air temperature sensor (DSS) failure
Backup operation
016
E403
Return air temperature sensor (RS) failure
Backup operation
016
E404
Data recorder return air temperature sensor (DRS) failure
Backup operation
017
E405
Discharge gas temperature sensor (DCHS1) failure
Backup operation
018
E406
Suction gas temperature sensor (SGS) failure
Backup operation
018
E407
Evaporator inlet temperature sensor (EIS) failure
Backup operation
018
E409
Evaporator outlet temperature sensor (EOS) failure
Backup operation
018
E411
Ambient temperature sensor (AMBS) failure
Alarm display only
019
E413
Low pressure transducer (LPT) failure
Backup operation
019
E415
High pressure transducer (HPT) failure
Backup operation
020
E417
Power voltage sensor (PT) failure
Alarm display only
021
E419
Current sensor (CT) failure
Alarm display only
022
E425
USDA #1 sensor failure
Alarm display only
022
E427
USDA #2 sensor failure
Alarm display only
022
E429
USDA #3 sensor failure
Alarm display only
023
E431
Humidity sensor (HuS) failure
Alarm display only
022
E433
Cargo temperature sensor (CTS) failure
Alarm display only
018
E435
Economizer inlet temperature sensor (ECO IN) failure
Backup operation
018
E437
Economizer outlet temperature sensor (ECO OUT) failure
Backup operation
017
E439
Discharge gas temperature sensor (DCHS2) failure
Backup operation
031
E441
CPU board temperature sensor failure
Backup operation
024
E607
Sheet key failure
Alarm display only
005
E701
Abnormal power supply voltage detected
Restart after 3 min.
025
E707
Temporary power supply shut down during operation
Restart after 3 min.
026
E801
CPU onboard battery failure
Alarm display only
027
E805
FA sensor failure
Alarm display only
028
E807
Ventilator open warning: Ventilator is open during frozen operation
Alarm display only
009
E809
Refrigerant shortage
Restart after 3 min.
029
E903
A communication error between CPU board (EC1) and operation
board (EC3)
Alarm display only
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-20
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-20
2016/02/02 17:17:35
2016/02/02 17:17:35
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...