2-21
●
Inverter F Alarm
Diagnosis
Alarm
code
Alarm content
Controller action
101
F528
E528 (Compressor does not startup) is generated 5 times.
UNIT stops
102
F52E
E52E (Temporary compressor overcurrent ) is generated 4 times.
UNIT stops
102
F52F
E52F (Compressor current sensor failure) is generated 4 times.
UNIT stops
103
F536
E536 (Current sensor offset error) is generated 4 times.
UNIT stops
103
F538
Inverter board failure (Microcomputer I/O port logic judgment
failure when unit is on)
UNIT stops
104
F53A
Incorrect setting (Controller model)
UNIT stops
102
F53B
Inverter board failure (EEPROM fault when unit is on
)
UNIT stops
103
F53C
E53C (Main circuit condenser recharging error) is generated 4 times. UNIT stops
101
F53D
E53D (Compressor lock) is generated 4 times.
UNIT stops
●
Inverter E Alarm
Diagnosis
Alarm
code
Alarm content
Controller action
101
E523
Compressor over current (>16.1A) is detected during operation.
Restart after 3 min.
101
E524
Compressor over current (>19A) is detected during operation.
Restart after 3 min.
101
E525
Actual frequency much lower than command frequency due to
compressor over load
Restart after 3 min.
105
E526
Actual frequency much higher than command frequency due to
external factors
Restart after 3 min.
101
E528
Compressor does not operate after startup.
Restart after 3 min.
106
E52C
Inverter board temperature higher than 99
℃
Restart after 3 min.
102
E52D
Inverter board temperature abnormal (> 150
℃
or < -45
℃
is
detected.)
Restart after 3 min.
102
E52E
Current is too high temporary during startup (over DC51A)
Restart after 3 min.
102
E52F
Compressor current sensor failure at startup
Restart after 3 min.
107
E531
Power supply voltage is unbalance
Restart after 3 min.
108
E532
Power supply voltage error (too high, too low at abnormally)
Restart after 3 min.
109
E533
Power supply voltage error (open phase)
Restart after 3 min.
103
E536
Current sensor offset fault when compressor starts
Restart after 3 min.
103
E53C
Main circuit charge failure when compressor starts
Restart after 3 min.
101
E53D
Compressor lock when compressor starts
Restart after 3 min.
110
E542
Cooling fan lock during operation (LX10F15A only)
Alarm display only
111
E5FF
A communication error between CPU board (EC1) and Inverter
board (EC8)
Restart after 3 min.
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-21
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-21
2016/02/02 17:17:36
2016/02/02 17:17:36
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...