2-35
022
E425
(
USDA1
)
・
E427
(
USDA2
)
E429
(
USDA3
)
・
E433
(
CTS
)
Alarm
Logic
When USDA sensor type "2" is set on
※
12 Configuration set in paragraph 2.3
≦
-39
℃
(320k
Ω
)
USDA
sensor
/
CTS or
≧
96
℃
(0.79k
Ω
)
Note: The alarm is activated when sensor or the circuit is disconnected (open) or short-circuited.
Possible
Causes
1. Incorrect setting (Setting number of USDA sensor is not match)
2. Circuit <line> malfunction
Connector disconnected / open wire / short circuit / USDA receptacle failure
3. USDA sensor failure
* Controller failure
Trouble
Shooting
Step 1. If USDA is set to "3" or "4" in
*
2 mode setting of paragraph 2.3, check whether all of
three or four sensors are connected.
Step 2. Check whether cable or receptacle between X6A and USDA receptacle is open or
short-circuited.
After make jumper between pins A
̶
B on USDA/CTS receptacle, check the continuity
on socket X6A (CPU board).
USDA1
USDA2
USDA3
CTS
X6A
(
CPU board
)
Sensor receptacle
(inside container)
7
5
3
1
8
6
4
2
Continuity check (Connector X6A
)
Repair or replace if there is disconnection or short circuit.
Step 3. Check the resistance value for each sensor of USDA and CTS sensor
USDA1
USDA2
USDA3
CTS
Replace sensor, if does not matches the resistance and USDA sensor
characteristic table.
Caution:
Regarding USDA sensor, type "1" and "2" have different characteristics.
Identify the type by referring
*
4 Configuration Information in paragraph
2.3 (configuration setting information).
Step 4. If the sensor is normal, replace the controller.
Controller
Action
E425
Alarm display only
E427
Alarm display only
E429
Alarm display only
E433
Alarm display only
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-35
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-35
2016/02/02 17:17:40
2016/02/02 17:17:40
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...