Alarm
Logic
&
Possible
Causes
Alarm Logic
Possible Causes
E52D
:
Fin temperature sensor failure
Inverter board failure
(
Fin temperature sensor
)
(
Fin temperature
≧
150
℃
or -45
≦℃)
F52E
:
E52E is generated 4 times.
E52E
:
Over current failure
Inverter board failure
(
IPM part
)
IPM
:
Intelligent Power Module
F52F
:
E52F is generated 4 times.
E52F
:
Compressor current sensor failure
Inverter board failure
(
Current detection part
)
F53B
:
EEPROM failure when unit is on
Inverter board failure (EEPROM part)
EEPROM : Electrically Erasable Program ROM
Trouble
Shooting
Replace Inverter board
Controller
Action
F52E, F52F, F53B
Unit stop
E52D
Restart after 3 minutes
E52E, E52F
Restart after 3 minutes (F52E, F52F is generated at 4 times retry.
)