2-43
106
E52C
Alarm
Logic
Inverter board temperature is over-heated (
≧
90
℃
with 260 sec elapse or
≧
99
℃
with 5 sec
elapse)
Possible
Causes
①
Ambient temperature is high
(
>50
℃)
②
Inverter board failure
(
fin temperature detection part
)
③
Inverter box is heat up due to less air circulation.
Trouble
Shooting
①
The unit can operate with an ambient temperature of up to 50
℃
.
Check for a short circuit at the discharge air of the air cooling condenser coil and also check
the surrounding environment. Operation continues if the environment is improved.
②
If no external factors are present, the inverter board may have failed. Replace the inverter
board.
③
Clean the fin on the rear of the inverter box and the base of the inverter box to ensure that
the air can circulate.
E52C
Restart after 3 minutes
107
E531
Alarm
Logic
Unbalanced power phase is supplied
Possible
Causes
Abnormal power supply
Trouble
Shooting
Regardless alarm is generated, restart after 3 minutes standby.
Operation continues if the external factor is improved.
E531
Restart after 3 minutes
108
E532
Alarm
Logic
Voltage in inverter becomes
≧
DC790V or
≦
DC320V due to power supply voltage
≧
AC530V or
≦
AC300V.
Possible
Causes
①
Power supply voltage is at high voltage (
≧
AC535V), or low voltage (
≦
AC300V).
②
Inverter board failure (Voltage detection part)
Trouble
Shooting
①
Check if the actual power voltage is within range (300V
〜
535V
)
.
*
Provide the power supply within range if it is out of range.
Restart after 3 minutes standby.
Operation continues if the power supply condition is improved.
②
If the power voltage is within range, it seems to be inverter board failure. Replace inverter
board.
Controller
Action
E532
Restart after 3 minutes
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-43
02章19-44̲LX10F11B3̲TR16-02̲En.indd 2-43
2016/02/02 17:17:42
2016/02/02 17:17:42
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...