Symptom
Cause
Checkpoint
Remedy
Ⅷ
The condenser f
an contin
ues to r
un.
The condenser fan
continues to run.
Temperature in the
control box is high.
YES
Is the condenser
fan stopped when the CBS
is cooled?
Closed WPS circuit
CBS OK
NO
NO
YES
Faulty WPS
Faulty CBS
*
CBS: Control box temperature sensor
The condenser fan continues to run.
Water pressure
switch WPS is
short-circuited.
Ⅸ
Others
The remote
monitoring
(RM) has no
output.
Disconnection of
TH3
YES
YES
Is there any short
circuit or disconnection on the
secondary side of RM receptacle
(on ship)?
Is there any short
circuit or disconnection on the
primary side of RM receptacle
(on unit)?
Standby until TH3 reset
Check the wiring on ship
⇒
Correct it.
NO
NO
NO
YES
Check the wiring.
⇒
Correct
Is fuse TH3
(automatic restore)
open?
Check for short circuit or disconnection between
X26A (I/O board) and RM receptacle
Check the I/O board.
⇒
Replace
Short-circuit of RM
circuit
Faulty controller
Short-circuit of RM
circuit on ship
2-53
02章45-54̲LX10F11B3̲TR16-02̲En.indd 2-53
02章45-54̲LX10F11B3̲TR16-02̲En.indd 2-53
2016/02/02 9:37:44
2016/02/02 9:37:44
https://daikin-p.ru
Summary of Contents for LX10F11B3
Page 7: ...https daikin p ru ...
Page 83: ...https daikin p ru ...
Page 93: ...https daikin p ru ...
Page 121: ...https daikin p ru ...
Page 129: ...https daikin p ru ...
Page 138: ...6 9 6 6 Sequence AIR WATER COOLED AIR WATER COOLED https daikin p ru ...
Page 139: ...6 10 Stereoscopic wiring diagram AIR WATER COOLED https daikin p ru ...