(4) Defrosting termination
Defrosting will be terminated when any one of the following three conditions is satisfied.
q
The below figure is satisfied during defrost.
Note) Table above shows the settings of Software Version 2407 or later.
Settings of Software Version 2406 or earlier come to the end conditions for 30 min. or later after
startup listed in Table above, regardless of operating time.
w
90 minutes have elapsed.
e
Any one of protective devices is activated.
※
Note : CSV is fitted only for LXE10E-1 but not for LXE10E-1A, 1B, 1C.
※
Note
Operating time
Status prior to defrosting
End conditions
Within 30 min.
after startup
Inside of range
EOS
>
30
℃
or EIS
>
85
℃
Outside of range
EOS
>
30
℃
or EIS
>
85
℃
30 min. or later
after startup
Inside of range
EOS
>
30
℃
or EIS
>
85
℃
Outside of range
EOS
>
30
℃
and RS/DRS
>
15
℃
or EIS
>
85
℃
001-030̲E-SM(LXE10E-1E)A4 2007.04.27 13:29 ページ 13
https://daikin-p.ru
Summary of Contents for LXE10E-1
Page 32: ...31 7 10 7 14 Schematic wiring diagram LXE10E 1E https daikin p ru...
Page 33: ...32 https daikin p ru...
Page 34: ...33 7 11 7 15 Stereoscopic wiring diagram LXE10E 1E https daikin p ru...
Page 35: ...34 https daikin p ru...
Page 49: ...48 2 22 2 5 4 3 12 RSV CSV DEHUMID LED 1 30 RH 95 RH LXE10E 1 LXE10E 1A https daikin p ru...
Page 55: ...54 4 6 1 2 P 4 3 P 3 56 3 L LP HP LXE10E 1 LXE10E 1A LXE10E 1 LXE10E 1A https daikin p ru...
Page 58: ...57 4 18 2 120 248 F EV EV 4 2 5 TEV VTX 3410DMS 1 120 248 F https daikin p ru...
Page 66: ...65 LXE10E 1E 7 10 https daikin p ru...
Page 67: ...66 https daikin p ru...
Page 68: ...67 LXE10E 1E 7 11 https daikin p ru...
Page 69: ...68 https daikin p ru...
Page 105: ...Parts related with option 3 Indoor fanguard K1 TR06 13 104 https daikin p ru...