2.4 OPERATION MODES AND CONTROL
The relationship between the operation mode and setting temperature is as follows.
Operation mode
Setting temperature
Control sensor
Operation description
Frozen mode
–10.1˚C to –30.0˚C
Return air
Compressor ON/OFF control
(13.82˚F to –22.0˚F)
temperature sensor
+30.0˚C to –10.0˚C
Supply air
Capacity control operation
Chilled mode
(+86.0˚F to –14.0˚F)
temperature sensor
with suction modulating valve
and hot-gas bypass control
Defrosting mode
–
–
Hot-gas defrosting with
refrigerant metering control