4
1. Operation Range
Use this unit in the following range.
Item
Operational range
Vibration/Shock
2G
Range of outdoor temperature
-30
°
C to +50
°
C (-22
<
to +122
<
)
Range of temperature inside
-30
°
C to +30
°
C (-22
<
to +86
<
)
Voltage
50Hz: 380/400/415VAC, 60Hz: 440/460VAC
Range of voltage fluctuations:
±
10%
2. Setting Temperature and Operation Mode
Operation mode
Frozen mode
Operation
procedure
Set the operating temperature to the
range of -10.1 to -30.0
°
C (+13.8 to -
22
<
).
Functions
Used to perform frozen operation,
which turns the compressor ON or
OFF and proportionally controls the
temperature inside by means of the
sensor of suction air temperature.
Operating temperature
Chilled mode
Partial frozen mode
Set the operating
temperature to the
range of +30 to -3.0
°
C
(+86 to +26.6
<
).
Set the operating
temperature to the range
of -3.1 to -10.0
°
C (+26.4
to +14
<
).
Used to perform chilled
operation, which
proportionally controls
the temperature inside
by means of the
sensor of discharge air
temperature.
Used to perform partial
frozen operation, which
proportionally controls the
temperature inside by
means of the sensor of
suction air temperature.
The evaporation fan performs High-operation.
The evaporation fan performs Low-operation.
3. Defrost Interval
Unlike standard units, this unit makes selection of the long-period setting timer or the short-period setting
timer in accordance with a lapse of time after the unit starts up.
●
Commencement of defrost operation
Within 72 hours after the unit
starts up.
From 72 hours onward after the unit
starts up.
Commencement of
defrost operation
The defrost operation is commenced
in accordance with a shorter period of
time set though either the short-
period setting timer (4 hours) or the
long-period setting timer.
The defrost operation is commenced
in accordance with a period of time
set though the long-period setting
timer.
01-08̲LXE10E-A37.qxd 2010.02.10 10:37 ページ 4
https://daikin-p.ru
Summary of Contents for LXE10E-A37
Page 11: ...9 7 Schematic wiring diagram LXE10E A37 https daikin p ru ...
Page 12: ...10 8 Stereoscopic wiring diagram LXE10E A37 https daikin p ru ...
Page 14: ...12 ሃ ჵ Ꮰ ත ˈ තߙ ݢ ȃ ၓ ፒ ܿ෭ ˈ כ ᅐ ძ ȃ ၫ ޡ ධძ ଓཨ ࡠ ძ ଓཨ ࡠ https daikin p ru ...
Page 17: ...15 5 ძ ɑ ძ ؠ ʗ ݢ ਾᅝ ن Ᏸ ʘި ධ ʙ ڗݢ ᏠᎧ 3 2 1 https daikin p ru ...
Page 27: ...25 4 コントロールボックス コントロールボックス内側 1 パソコンポートレセプタクル 2 サーキットブレーカ 3 乾電池組立品 3 2 1 https daikin p ru ...
Page 31: ...29 7 シーケンス LXE10E A37 https daikin p ru ...
Page 72: ...70 MEMO https daikin p ru ...