4-22
4.2.10 High-pressure switch (HPS)
●
Model ACB-KB15
●
Set point OFF : 2400kPa (24.47kg/cm
2
)
ON
: 1900kPa (19.37kg/cm
2
)
When the refrigeration pressure of the unit
rises abnormally, the compressor stops for
safety. The HPS will be activated when the
pressure exceeds the set point, as a result of
trouble with the condenser fan.
(1) Replacement procedure
q
Disconnect the lead wire from the control
box.
w
In order to prevent refrigerant from flowing
out, disconnect the high-pressure gauge
piping from the gauge joint (with check valve)
A on the compressor side.
e
Remove the flare nut B and mounting
screws of HPS on the casing at the left side
of the compressor.
r
Replace the HPS. After tightening the flare
nut B , tighten the flare nut A .
t
After tightening A , slightly loosen the flare
nut B , remove air, and retighten B .
y
After replacing, carry out the refrigerant
leakage check, and make sure that there are
no leaks.
C O M P R E S S O R
L P T
L
S
P
H
T
P
H
Disconnect flare
nut here when
replacing HPS, HPT.
Disconnect flare nut here
when replacing LPT.
B
A
C
4.2.11 Low pressure transducer (LPT)
The LPT is located in the refrigerant circuit.
The operating low pressure value is displayed
on the controller indication panel.
(1) Replacing the transducer
q
Disconnect the lead wire from the control box.
w
In order to prevent refrigerant from flowing
out, disconnect the low-pressure transducer
piping from the gauge joint (with check valve)
○
C
on the compressor side.
e
Remove two screws on the clamp plate fixing
low pressure transducer in place, and cut the
binding bands.
CAUTION
Do not expose the low pressure
transducer to hot air of a dryer for
excess time.
Otherwise, the transducer may be damaged.
t
Insert the pressure transducer cable through
the heat shrinkage tube, and connect the
union joint and connector to the new low
pressure transducer. If paint on the low
pressure transducer is peeled off, apply clear
lacquer.
r
Remove the heat shrinkage tube, and
disconnect the connector from the low
pressure transducer.
Flare nut
Union joint
Low pressure transducer
Heat shrinkage tube
¡
NSK-BC010F
Flare nut
Union joint
Low pressure transducer
Model
NSK
Transducer type
NSK-BC010F
Identification
color
Transducer
Black body
Connector
Nothing
q
Clamp plate
w
Binding band