2. OPERATION SETTING MODE
Control temperature, defrosting interval, and control humidity (optional) can be set.
3-8
To change to the OPERATION SETTING MODE, press the
key while
the unit is in the CURRENT INDICATION MODE.
In the OPERATION SETTING MODE, Control temperature, Control
humidity (optional) and Defrosting interval can be set.
S
Select an item using the
key. The value of the selected item is indicated on the LED and LCD display.
S
Note 1)
●
When the humidity control is not set, this indication does not appear.
Note 2)
●
In case temperature is set in ˚C setting temperature can be set at interval of 0.1 ˚C.
In case temperature is set in ˚F, setting temperature should be the value converted into ˚F based on
˚C and rounded off the two decimal places.
LED display
Current setting
temperature
Note 2)
Current setting
humidity
Current defrosting
interval
LED display
"SET-SPC" or "SET-
SPF"
"SET-SHU"
"SET-dEF"
Setting method
Change the value using the key
or key. Press the key to
confirm the setting.
Setting temperature range; –30 to 30˚C.
Change the value using the key
or key. Press the key to
confirm the setting.
Setting humidity range: 60 to 95%RH
Select a defrost interval 99h, 24h,
12h, 9h, 6h, or 3h using key
or key. Press the key to
confirm the setting.
"On demand defrosting" is
conducted when "99h" has been
selected. (See page 2-21.)
Item
–
–
–
key or no key operation for 5 minutes
CURRENT INDICATION
MODE
S
CONTROL
TEMPERATURE SETTING
S
S
CONTROL HUMIDITY
SETTING
(optional Note 1)
S
DEFROST
INTERVAL SETTING
S
I/O ON
Power off
Unit off
All Lighting
(for 3 sec.)
Preparation
(for 18 sec.)
Current
indication
※
1
Circuit Breaker ON
※
2
Operation Setting (Set Point ˚C, Humidity %, Defrost Internal)
or no key operation for 5 min.
https://daikin-p.ru