14
|
Configuration
Installer and user reference guide
75
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
Remote controller field settings
Mode
SW
SW description
Value
Default value
R1
3
Controller thermistor
adjustment (Cooling)
0
: –3.0°C,
1
: –2.5°C,
2
: –2.0°C,
3
: –1.5°C,
4
: –1.0°C,
5
: –0.5°C,
6
: ±0°C,
7
: +0.5°C,
8
: +1.0°C,
9
: +1.5°C,
10
: +2.0°C,
11
: +2.5°C,
12
: +3.0°C
6
4
Controller thermistor
adjustment (Heating)
0
: –3.0°C,
1
: –2.5°C,
2
: –2.0°C,
3
: –1.5°C,
4
: –1.0°C,
5
: –0.5°C,
6
: ±0°C,
7
: +0.5°C,
8
: +1.0°C,
9
: +1.5°C,
10
: +2.0°C,
11
: +2.5°C,
12
: +3.0°C
6
5
Controller thermistor
adjustment (Auto)
0
: –3.0°C,
1
: –2.5°C,
2
: –2.0°C,
3
: –1.5°C,
4
: –1.0°C,
5
: –0.5°C,
6
: ±0°C,
7
: +0.5°C,
8
: +1.0°C,
9
: +1.5°C,
10
: +2.0°C,
11
: +2.5°C,
12
: +3.0°C
6
6
Controller thermistor
adjustment (Fan only)
0
: –3.0°C,
1
: –2.5°C,
2
: –2.0°C,
3
: –1.5°C,
4
: –1.0°C,
5
: –0.5°C,
6
: ±0°C,
7
: +0.5°C,
8
: +1.0°C,
9
: +1.5°C,
10
: +2.0°C,
11
: +2.5°C,
12
: +3.0°C
6
7
Home screen
0
: Detailed
1
: Standard
1
8
Backlight no-operation timer
0
: 5 seconds
1
: 10 seconds
2
: 20 seconds
0
9
Status indicator faintness
0
: 0% (OFF),
1
: 1%,
2
: 2%,
3
: 3%,
4
: 5%,
5
: 7%,
6
: 9%,
7
: 11%,
8
: 13%,
9
: 15%,
10
: 17%,
11
: 20%
9
10
Backlight faintness
0
: 0% (OFF),
1
: 1%,
2
: 2%,
3
: 3%,
4
: 4%,
5
: 5%,
5
11
Status indicator mode
0
: Normal
1
: Hotel setting 1
2
: Hotel setting 2
2
13
Bluetooth Low Energy
advertising
0
: Always advertising
1
: Enable manually
0