15
|
About the app
Installer and user reference guide
116
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
INFORMATION
To use this function, it is required that digital input adapter BRP7A5* is part of the
system.
▪
Make sure that the digital input adapter and its optional contacts (window
contact B1 and key card contact B2) are correctly installed. Confirm that the
voltage free contact of the digital input adapter is in the correct position. For
instructions on how to install the digital input adapter, see the installation manual
of the digital input adapter.
▪
When the digital input adapter does not function properly, external input
interlock is not available in the menu.
▪
When the digital input adapter is part of the system, the system does not allow
for the connection of a slave controller.
▪
When the digital input adapter is part of the system, it is not possible to use the
Schedule function.
▪
When the digital input adapter is part of the system, as well as a centralised
controller, the external input interlock function is controlled by the centralised
controller, and not by the adapter.
15.5.8 Maintenance
R32 refrigerant settings
R32 refrigerant system settings
The refrigerant leak alarm can be tested using the Madoka Assistant app.
1
In the app, navigate to R32 refrigerant settings in the Maintenance section
under Unit settings.
2
Tap R32 refrigerant system settings.
3
Tap Test alarm and blinking LED to test the refrigerant leak alarm.
Result:
The refrigerant leak alarm starts.
4
Tap Stop testing alarm and blinking LED to stop the alarm.
Result:
The refrigerant leak alarm stops.
Supervised room address
Assign a unique supervised room address to individual indoor units. It is mandatory
to set a unique supervised room address for every indoor unit when the remote
controller is set to “Supervisor” mode. First select an indoor unit by way of its unit
number, then assign a unique supervised room address to it. If the supervised
room address is not set, alarms will not be communicated to the remote controller
in “Supervisor” mode.
To set the supervised room address in the Madoka Assistant app, navigate to R32
refrigerant settings in the Maintenance section under Unit settings. Then, tap
Supervised room address to manage the supervised room address of the indoor
units.
Errors and warnings
Consult the error history, and temporarily enable/disable the pushing of error and/
or warning notifications.
The pushing of error and warning notifications is by default enabled. Disable
"Display errors" and "Display warnings" to prevent the system from pushing error
and warning notifications for 48 hours. After 48 hours, "Display errors" and
"Display warnings" become automatically enabled again.