5
|
Operation
Installer and user reference guide
23
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
Single setpoint
Dual setpoint
C2
+ C1
SP
+ C1
C2
+1°C
-1°C
-1°C
+1°C
24°C
23°C
21°C
20°C
22°C
The system is heating up the room.
When the room temperature rises
above C2 (24°C) while the guard timer is
still running, a changeover is forced
from Heating to Cooling.
The system is cooling down the room.
When the room temperature drops
below C2 (20°C) while the guard timer is
still running, a changeover is forced
from Cooling to Heating.
+1°C
+1°C
-1°C
-1°C
DIFF: 2°C
C2
+ C1
SP
+ C1
C2
SP
26°C
25°C
24°C
21°C
20°C
22°C
The system is heating up the room.
When the room temperature rises
above C2 (26°C) while the guard timer is
still running, a changeover is forced
from Heating to Cooling.
The system is cooling down the room.
When the room temperature drops
below C2 (20°C) while the guard timer is
still running, a changeover is forced
from Cooling to Heating.
INFORMATION
To prevent operation mode changeovers from occurring too frequently, changeovers
typically occur only after the guard timer has run out (i.e. Case 1). However, to
prevent the room from getting too hot or too cold, a changeover is forced when the
room temperature reaches C2 while the guard timer is still running (i.e. Case 2).
5.2.2 To set the operation mode
1
Navigate to the operation mode menu.
2
Use and to select an operation mode.
3
Press to activate.
Result:
The indoor unit changes its operation mode and the controller returns to
the home screen.
5.3 Setpoint
The setpoint is the target temperature for the Cooling, Heating, and Auto
operation modes.